Consistent Refrigerant Drying with An Energy Saving Benefit

  • overview
  • benefits
  • function
  • sizing
  • download
  + 1: ALUMINUM HEAT EXCHANGER
Vertical profile allows for minimum pressure drop and self cleans using gravitational force
   
  + 2: STANDARD BEKOMAT® DRAIN
Reliable condensate discharge and maximum energy savings
   
  + 3: VARIOFLOW HOT GAS BY-PASS VALVE
Stable dew point regardless of varying operating conditions - patented design
   
  + 4: LARGE CROSS SECTION OF FLOW CHANNELS
Low velocities, reduced power input
   
  + 5: MAINTENANCE FRIENDLY
The compact design and open frame provides easy access to all components
   
 1  warm, moisture saturated compressed air is cooled down to +37 °F. The generously dimensioned heat exchanger enables particularly effective cooling, while the flow resistance is reduced to an absolute minimum.
2 Contrary to conventional systems, the movement of air through the heat exchanger follows a downward pattern. The effects of gravity produce an exceptionally high droplet separartion efficiency. In the large condensate collection space, the flow velocity is greatly reduced. Re-entraining of previously separated droplets is thus reliably prevented.
3 Before leaving the dryer unit, the dried, cold compressed air is reheated in an air-to-air heat exchanger. During this process, the relative humidity of the air is lowered considerably and the same time up to 60% of the cooling energy is recovered.
4 The separated condensate is discharged, without wastage of compressed air, from the DRYPOINT® RA refrigeration dryer into the level-controlled BEKOMAT® condensate drain. It can then be treated according to requirements, for example, in an QWIK-PURE® or ÖWAMAT® oil/water separation system or a BEKOSPLIT® emulsion splitting plant.
 
Model Name Capacity (scfm) Connection Size Height Width Depth Weight
RA 10-NA 10 3/8" 17 14 12 52
RA 15-NA 15 1/2" 19 22 15 58
RA 20-NA 20 1/2" 19 22 15 62
RA 35-NA 35 1/2"
19 22 15 66
RA 50-NA 50 1/2" 19 22 15 70
RA 75-NA 75 1" 29 17 14 90
RA 100-NA 100 1 1/4" 29 17 14 98
RA 125-NA 125 1 1/4" 33 17 19 105
RA 150-NA 150 1 1/4" 33 17 19 110
RA 200-NA 200 1 1/2" 35 21 20 125
RA 250-NA 250 1 1/2" 35 21 20 140
RA 300-NA 300 2" 36 22 21 240
RA 350-NA 350 2" 36 22 21 250
RA 400-NA 400 2 1/2" 37 24 22 265
RA 500-NA 500 2 1/2" 37 24 22 300
RA 600-NA 600 3" Flange 59 38 31 405
RA 800-NA 800 3" Flange 59 38 31 420
RA 1000-NA 1000 3" Flange 59 38 31 600
RA 1250-NA 1250 3" Flange 59 41 31 620
RA 1500-NA 1500 4" Flange 73 61 53 1200
RA 1750-NA 1750 4" Flange 73 61 53 1300
RA 2000-NA 2000 4" Flange 73 61 53 1350
RA 2500-NA 2500 4" Flange 73 61 53 1450
RA 3000-NA 3000 6" Flange 73 89 55 1750
RA 4000-NA 4000 6" Flange 73 89 55 1850
RA 5000-NA 5000 6" Flange 68 61 104 2040
DRYPOINT RA Documents
In this section you will find all of the available electronic media related to this particular product. This includes the official releases of brochures, manuals, data sheets, and technical drawings (where available) that are free for public use. To download, either follow the link to open the file and select "Save As..." from the program menu or please right click on the link and select "Save Target As..."
PDF Files
Opening these files requires Adobe® Reader®. To download the latest version, please click the icon.

Brochures
Brochure (U.S. Version, English)
PDF File (423 KB)
Manuals
DPRA 10-100
PDF File (1.30 MB)
DPRA 125-400
PDF File (1.48 MB)
DPRA 200-2500
PDF File (2.96 MB)
DPRA HT 20-350 (high inlet temperature)
PDF File (2.04 MB)
DPRS HP 15-1700 (high pressure)
PDF File (3.83 MB)
Data Sheets
Not Available
Technical Drawings
DRYPOINT RA AutoCAD (.dxf)
WinZip File (1.05 MB)
DRYPOINT RA Dimensional Drawings
PDF File (568 KB)